Float Switch Selection Guide: Cable, Rod & Side-Mounted Level Switches
How to choose a float switch or water level controller: contact type, voltage and current rating, cable length, material, IP rating, and how to specify for
A float switch is the cheapest, most robust way to detect a liquid level and switch a pump, valve or alarm without electronics in the wet end. For panel builders, OEMs, water-treatment packagers and importers buying from Asia, the part number is decided by the medium, the voltage the contacts must break, and how the float is mounted. This guide covers the parameters that actually change the model, so the switch you specify survives the liquid it sits in.
1. What a float switch actually does
Inside the sealed float is a tilt- or position-sensitive mechanism (a mercury-free rolling ball or a reed switch) that opens or closes a contact when the liquid lifts the float past its trip angle. There is no controller to program and almost nothing to fail, which is why floats still outlast far more expensive sensors in sumps, tanks and boreholes. The two jobs are level detection (tell me when the tank is full or empty) and direct load switching (turn the pump or solenoid on or off).
2. Mounting styles
- Cable float (pendant): a moulded float on a flexible cable, hung into the tank. Cheap, adjustable by cable length and tie-off point, ideal for sewage pits and sumps.
- Vertical stem / rod float: a float rides up and down a fixed rod; compact and stable, good for narrow tanks and control panels with limited headroom.
- Side-mounted: bolts to the tank wall at a fixed point; used where a pendant would tangle or where the level point is fixed.
- Miniature / micro float: for appliances, humidifiers and small vessels where space is tight.
3. The electrical rating is the real limit
The contacts must break the actual load, not just signal a PLC. Check both numbers on the datasheet:
| Parameter | What to specify |
|---|---|
| Contact rating | e.g. 10(8) A at 250 V AC / 24 V DC — must exceed the pump or valve inrush |
| Contact form | NO (normally open) for "fill", NC (normally closed) for "drain" |
| Signal vs power | low-current versions only for PLC input; power versions switch the load directly |
A switch sized only for a 24 V signal will weld its contacts the first time it tries to break a 1.5 kW pump. Always match the rating to the load it switches, with margin for motor inrush.
4. Material vs the medium
The body spends its life submerged. Match it to the liquid:
- PP (polypropylene): clean and mildly dirty water, most sumps and cisterns.
- POM / nylon: oils, light chemicals, where PP is not chemical-resistant.
- 316 stainless steel: food, pharmaceutical and corrosive or high-temperature duty.
- NBR / FKM seals: for oil and hydrocarbon media.
Also confirm the specific gravity the float is calibrated for — a float tuned for water will not trip in a light oil, and one tuned for heavy slurry may never sink in clean water.
5. Cable, temperature and ingress
Specify the cable length to reach from the mounting point to the controller with slack for the trip angle, and choose the sheath: neoprene or PVC for water, oil-resistant for pits. The ingress rating should be at least IP68 for continuous submersion, and the temperature range must cover both the liquid and any steam or frost above it.
6. Fill vs drain logic
A float used to stop overflow (turn the pump off when full) needs a normally-closed contact that opens at high level; one that empties a pit (pump on when empty) needs normally-open. Two floats give hysteresis — a high switch to start the pump and a low switch to stop it — so the pump does not short-cycle. Get the logic backwards and the pit overflows or the pump runs dry.
7. What to put on the RFQ
- Medium (water, sewage, oil, chemical) and its specific gravity.
- Load the contacts switch: voltage, AC/DC, current including inrush.
- Contact form and logic: NO/NC, fill or drain.
- Mounting: cable pendant, vertical rod, or side-mount, with cable length.
- Body material and seal compound for the medium and temperature.
- IP rating and any approvals (CE, potable-water, ATEX for hazardous areas).
ELEHPD supplies cable and rod float switches in PP, POM and stainless bodies with IP68 ratings, NO/NC contacts and leads sized for direct pump control, built to IEC practice and ready to drop into sumps, cisterns, boreholes and OEM water systems.
FAQ
Can a float switch run a pump motor directly?
Only when the contact rating comfortably exceeds the motor inrush. A small pump up to the contact rating (for example 10(8) A at 250 V AC) can be switched directly; above that, or for three-phase motors, use the float as a signal into a contactor or relay so the contacts only carry the coil current.
What cable length should I order?
Base it on tank depth plus the hysteresis you need between the fill and empty points. Add roughly 0.5-1 m of slack for the tie-off and for future level adjustment, and remember a longer cable lowers the trip point - order the standard lengths (2, 3, 5, 10, 20 m) rather than cutting to an odd length.
Which float switch suits sewage or dirty water?
Use a heavy-duty cable (pendant) float with an oil- and chemical-resistant jacket, IP68 sealing, and a free-hanging weight so the float cannot be trapped by sludge. Avoid side-mounted units in silting pits, and specify a contact form that fails safe if the float is blocked.
Related ELEHPD products
- CX-M15-3 float switch water level controller
- CX-M15-4 float switch water level controller
- CX-M15-6 float switch water level controller
- CX-M15-7 float switch water level controller
- CX-M15-8 float switch water level controller
- CX-80AB float switch flow sensors water level
- Electrical M15-5 Ball Float Liquid Level
- Water level controller for pump red black
Related product categories
Talk to us about your specification
Send the ratings, dimensions and quantities you are working to and we will confirm the closest match from the ELEHPD catalogue, the compliance documents available for it and the lead time. OEM branding, private model numbering and buyer-specific cartons are available on qualified volumes.